Download materials
Download materials
Residual Current Device DRB
CÓD: DRB100-203
Description
Description
Residual Current Device (RCD) for protection against current leakage in higher-capacity electrical installations. Suitable for industrial and commercial applications, ensuring the safety of people and equipment. Available in two-pole and four-pole versions. Offers high reliability and performance.
- Protection against current leakage
- Sensitivity of 30 mA or 300 mA
- Two-pole and four-pole versions
- Currents of 80 and 100A
Select the options below
Code list
Code list
| Code | Description |
|---|---|
| DRB100-203 | 100A / Bipolar / 30mA |
| DRB100-430 | 100A / Bipolar / 300mA |
| DRB80-230 | 80A / Tetrapolar / 300mA |
General specifications
General specifications
| Poles | 2 | 4 |
|---|---|---|
| Rated voltage (Ue) | 230V - 50 / 60Hz | 400V - 50 / 60Hz |
| Weight | 206g | 384g |
| Standards | IEC/EN61008-2 | |
| Rated current (In) | 25, 40, 63, 80 or 100A | |
| Class | AC | |
| Sensibilidade nominal IΔn | 30mA or 300mA | |
| Insulation voltage Ui | 500V | |
| Rated making and breaking capacity IΔm | 500 (In=25A/40A), 630 (In=63A) or 1000 (In=80A/100A) | |
| Rated short-circuit current IΔc | 6kA (80 ~ 100A) / 10kA (25 ~ 63A) | |
| Time of opening under IΔm | ≤ 0.1 seg / sec | |
| Pollution degree | 2 | |
| Electrical life | 2 x 10³ operations | |
| Mechanical life | 2 x 10³ operations | |
| Current fault indicator | Included | |
| Operating temperature | -5 ~ 40°C | |
| Storage temperature | -25 ~ 70°C | |
| Degree of protection | IP20 | |
| Connection type | Cable and/or pin-type connection comb | |
| Screw tightening torque | 2.5Nm | |
| Mounting | DIN rail TS35 | |
| Model | DRA: 25, 40 or 63A DRB: 80 or 100A | |