Download materials
Download materials
Emergency Stop Safety Relay RPE-P
CÓD: RPE-P
Description
Description
The RPE-P Safety Relay is designed for the safe monitoring of emergency stop devices and safety components, such as emergency stop buttons, light curtains, safety interlock switches, and magnetic sensors. It features dual channel with redundancy, short-circuit monitoring, and monitored reset, meeting Category 4, PL e, and SIL 3 safety requirements.
- Category 4, PL e / SIL 3
- Dual channel with redundancy
- Short-circuit monitoring
- Manual or automatic reset
General specifications
General specifications
| Model | RPE-P |
| Function | Emergency stop (E-Stop) |
| Supply power | 24 VDC |
| Voltage range | 85% to 110% |
| Power consumption | < 3 W |
| Input | Dual-Channel |
| Safety contacts | 3 NO (13-14 / 23-24 / 33-34) |
| Auxiliary contacts | 1 NC (41-42) |
| Switching capacity | AC15: 5 A / 250 VAC DC13: 6 A / 24 VDC |
| Contact resistance | ≤ 100 mΩ |
| Status display | 3 Green LEDs |
| Mechanical life | 10,000,000 operations |
| Rated thermal current | 5 A |
| Short-Circuit protection | 6 A fast or 4 A slow |
| Response time (max.) | 10 ms |
| Cross-Circuit detection | Yes |
| Diagnostic coverage (DC) | 99% (High) |
| Probability of dangerous failure per hour (PFHd) | 2.80 × 10⁻¹⁰ 1/h |
| Stop category | CAT0 |
| Safety rating | Cat. 4 / PLe / SIL 3 |
| Approvals / Certifications | CE / ISO / SIL3 / PLe |
| Applicable Standards / Compliance | BS EN 62061: 2015 SO 13849-1: 2015 ISO13849-2: 2012 |
| Safety integrity level (SIL) | SIL 3 (in accordance with BS EN 62061: 2015) |
| Performance level (PL) | PLe (in accordance with ISO 13849-1: 2015) |